Series 65 incorporates well-proven sensing technologies, including an Integrated Circuit based on that used in XP95 analogue addressable detectors. The Series 65 range has a wide operating voltage of 9–33V and consists of ionisation, integrating ionisation and optical smoke detectors, four grades of heat detector and a range of bases.
Brand Features
Wide-operating voltage of 9–33 V DC Wide-operating and storage temperature of -20°C to +60°C Can be used on security systems Electrically and mechanically compatible with Series 60 Proven detection performance
Operation
The detector has a moulded self-extinguishing white polycarbonate case with wind resistant smoke inlets. Nickel plated stainless steel wiper contacts connect the detector to the base. Inside the detector case a printed circuit board has the ionisation chamber mounted on one side and the signal processing electronics on the other. The ionisation chamber consists of a reference chamber contained inside a smoke chamber. The outer smoke chamber has inlet apertures fitted with insect resistant mesh. The radioactive source holder and smoke chamber form positive and negative electrodes respectively. An Americium 241 radioactive source mounted within the reference chamber irradiates the air in both chambers, producing positive and negative ions. A voltage across the electrodes produces an electric field. Ions are attracted to the electrode of the opposite sign to their own charge. Many recombine but a small electric current flows between the electrodes. At the junction between reference and smoke chambers the sensing electrode converts variations in chamber current into voltage changes. When smoke particles enter the ionisation chamber ions become attached to them with the result that the current flowing through the chambers decreases. This effect is greater in the smoke chamber than in the reference chamber, and the imbalance causes the sensing electrode to become more positive. The voltage at the sensing electrode is fed to a comparator where it is compared with a factory-set clean air reference voltage. If the monitored voltage exceeds the reference voltage, the comparator switches the alarm latch on, increasing the current drawn from the supply from about 40μA to a maximum of 75mA. This fall in the impedance of the detector is recognised by the control panel as an alarm signal. The alarm latch current also illuminates the detector integral LED. A remote indicator connected between the L1 IN terminal and the –R terminal will have a voltage equal to the supply voltage less 1 volt across it and so will illuminate. See page 17 for details of the remote indicator. To ensure correct operation of the detector the control panel must be arranged to supply a maximum of 33 volts DC and a minimum of 9 volts DC in normal operation. The supply may fall to 6 volts DC in alarm conditions if a supply current of at least 10mA is available at this voltage. To ensure effective illumination of the integral LED and any remote indicator, the supply to the detector should exceed 12 volts. To restore the detector to quiescent condition, it is necessary to expel any smoke and interrupt the electrical supply to the detector for a minimum of one second.
Options
(Apply to standard and integrating versions) 1. Flashing LED: The alarm-indicating LED flashes when the detector is in a quiescent state. 2. Magnetic test switch and Flashing LED: A magnetic test switch in the circuit of the detector can be magnetically activated from outside the case to initiate an alarm condition for test and commissioning purposes. A flashing LED, as outlined above, is also included.
Environmental Characteristics
Series 65 ionisation smoke detectors operate over a temperature range of –20°C to +60°C. Ionisation detectors have some sensitivity to air movement (wind). The extent to which the sensor output will change depends on the wind speed and on the orientation of the detector relative to the wind direction. Relatively small changes in wind direction can cause significant changes in sensor output. For wind speeds up to 1m/s (200ft/min) sensitivity will change by less than 20%. Continuous operation in wind speeds greater than 2m/s (400ft/min) is not recommended. However, wind speeds up to 10m/s (2000ft/min) can be tolerated for short periods and will not under any conditions increase the probability of false alarms. Series 65 ionisation smoke detectors are supplied in individual packing with a red lid serving as a dust cover which can be left in place after fitting to prevent ingress of foreign material until commissioning of the system takes place. At this point the covers must be removed.
Product Information
Ionisation detectors use a low activity radioactive foil to detect fires by irradiating the air in the smoke chamber and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm. Circuitry in the Integrating Ionisation Smoke Detector protects against transient levels of smoke above the normal threshold for up to 20 seconds.
Key Features
Responds well to fast burning, flaming fires Designed to operate in environments where transient levels of smoke may be expected Wide-operating voltage Flashing LED and magnet operated test switch option.
General |
Applications |
- B&Bs/guest houses
- Cafes
- Restaurants
- Retail
- Small to medium buildings
|
Fire Type |
Fast burning, flaming fires |
Warranty |
10 year |
Performance |
Chamber type |
Chevron |
Electrical |
Polarity |
L1 & L2 are polarity insensitive |
Radioactive isotope activity |
33.3kBq |
Alarm current (at 24 volts) |
52mA |
Holding voltage (min) |
6V |
Minimum voltage to light alarm LED |
12V |
Alarm reset time |
1s |
Alarm load |
420Ω in series with 2V drop |
Environmental |
Humidity (min) |
0% RH |
Humidity (max) |
95% RH |
Humidity Note |
no condensation or icing |
Humidity |
0% to 95% (no condensation or icing) |
Operating temperature (min) |
-20°C |
Operating temperature (max) |
60°C |
Operating temperature |
-20 to 60°C |
IP rating Value |
IP23D |
Storage temperature (min) |
-30°C |
Storage temperature (max) |
80°C |
Storage temperature |
-30 to 80°C |
Conformance |
Standards |
EN 54-7 |
Approvals |
|
Mechanical |
Weight |
102g |
Colour |
White |
Materials housing |
Polycarbonate |
Materials terminals |
Nickel plated stainless steel |
Product length |
42mm |
Product diameter |
100mm |
Detection principle |
Ionisation chamber. |
Sensor configuration |
Twin compensating chambers using one single sided ionising radiation source. |