Warranty |
10 year |
Applications |
B&Bs/guest houses
Bedrooms
Cafes
Restaurants
Retail
Small to medium buildings |
Fire Type |
Slow burning, smouldering fires |
Colour |
White |
Sensor configuration |
Horizontal optical bench housing infra-red emitter and sensor, arranged radially to detect forward scattered light. |
Weight |
99g |
Materials housing |
Polycarbonate |
Materials terminals |
Nickel plated stainless steel |
Product length |
42mm |
Product diameter |
100mm |
Detection principle |
Photo-electric light scattering. |
Product length |
1.65in |
Product diameter |
3.94in |
Standards |
EN 54-7 |
Approvals |
CPR
LPCB
UL |
Chamber type |
Chevron |
Power-up surge current |
0.115mA |
Maximum power-up time |
30 seconds |
Status indicator - Alarm |
Red |
Status indicator - Fault |
Off |
Quiescent current |
50μA |
Quiescent current tested at |
24V dc |
Supply voltage (max) |
33V dc |
Supply voltage (min) |
9V dc |
Supply voltage (Vmin-Vmax) |
9 to 33V dc |
Terminal functions L2 |
-L2 Line in & out negative |
Terminal functions L1 in |
+L1 in |
Terminal functions L1 out |
+L1 out |
Terminal functions -R |
-R Remote indicator negative connection |
Polarity |
L1 & L2 are polarity insensitive |
Battery powered |
No |
Sampling frequency |
Once every 3 seconds |
Holding voltage (min) |
6V
|
Minimum voltage to light alarm LED |
12V |
Alarm reset time |
1s |
Alarm load |
420Ω in series with 2V drop |
Humidity (max) |
95% RH |
Humidity (min) |
0% RH |
Humidity Note |
no condensation or icing |
Humidity |
0% to 95% (no condensation or icing) |
Operating temperature |
-20 to 60°C |
Operating temperature (max) |
60°C |
Operating temperature (min) |
-20°C |
IP rating Value |
IP23D |
Storage temperature (max) |
80°C |
Storage temperature (min) |
-30°C |
Storage temperature |
-30 to 80°C |
Effect of wind speed |
None |
Operating temperature |
-4 to 140°F |
Operating temperature (max) |
140°F |
Operating temperature (min) |
-4°F |