C-Tec CFP Standard 2 Zone Conventional Fire Alarm Panel

Certified to EN54 parts 2, 4 and 13, C-TEC’s CFP 2 zone conventional fire alarm panel offers an array of user and installer-friendly features at a very competitive price.

Supplied in an attractive flush or surface mountable plastic enclosure, it includes two detector zones, four conventional sounder circuits, class change and alert inputs, on-board fire and fault relays and combined keypad/keyswitch entry.

A wide range of engineering functions are also provided including selectable zone delays, coincidence and non-latching zone facilities. Comprehensive test and fault finding facilities are also provided.

Optional repeaters and relay expansion boards also available.

  • Third-party certified to EN54 parts 2 and 4 by the Loss Prevention Certification Board (LPCB) and EN54 part 13 certified by Kiwa Telefication.
  • Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry.
  • Manufactured by C-TEC in the UK.
  • Two detector zone circuits.
  • Four conventional sounder circuits*
  • Integral 1.5A EN54-4/A2 compliant switch mode PSU.
  • Wide range of engineering functions including zone test, coincidence, zone delay and non-latching zones.
  • Two on-board relays (Fire and Fault).
  • Two open-collector outputs (Remote and Reset).
  • ‘Class change’ and alert inputs.
  • Installer-friendly design.
  • Attractive flush or surface mountable plastic lid and enclosure – no bezel required.
  • Low 25mA quiescent current.
  • Multiple indicators.
  • System expansion connections provided for up to eight two-wire repeaters (one CFP761 network card required per system) and optional CFP relay boards.
  • Space for two x 12V 3.3Ah VRLA batteries.
  • Fully compatible with C-TEC’s ActiV fire detectors, sounders and visual alarm devices.
Approvals/certifications

Certifed to EN54 Parts 2 & 4 by the LPCB., Certified to EN54-13 by Kiwa Telefication.

Mains supply

230V 50/60Hz.

Mains rated current

350mA maximum.

Internal power supply

19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).

Total output current limited to

1.5A @ 230Vac (ImaxA eq 146mA).

Quiescent current

25mA (mains failed, internal sounder active, PSU & gen fault LED lit)

Max battery size and type

2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah.

No. of detector zone circuits

2 (Max. length per circuit is 500m).

Call point resistor value

470 to 680Ω.

Max. devices per detector zone

25 detectors (or 32 detectors/manual call points combined).

No. of conventional sounder circuits

4 (Max. length per circuit is 500m).

EOL resistor value

6800Ω 5% Tol. 0/25W (blue, grey, red, gold).

Alarm voltage

27V max, 20V min (final battery voltage)

Max. sounder output current

4 x 200mA (800mA total).

Auxiliary relays

Two: (1) Aux. Fire; (2) Fault. Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.

Open collector outputs

Two: (1) Reset (Active during reset cycle); (2) Remote (Active during any unsilenced fire condition provided all relevant delays have expired). Max. sink current 30mA, Max. open circuit voltag

Other outputs

24V Aux. Power (Protected by a resettable fuse. 100mA min. hold current. Resets when fault removed).

Auxiliary inputs

Two: (1) ‘Class Change’ (constant sounders); (2) Alert (pulsed sounders). Connect to 0V to trigger, Max. input voltage 27V (non-latching)

Engineer (AL3) functions

Program coincidence (double knock); Invoke One Man Walk Test; Program delays; Set up zones for non-latching operation; Program sounders to resound (or not resound) when a new zone enters al

Expansion connections

Yes – for optional network driver cards (one required per repeater system), relay output cards and EN54-13 sounder circuit interface boards.

Product dimensions (mm)

380 W x 235 H x D 96mm (hole required for flush mounting = 367 W x 220 H x 75 D mm. No bezel required).

Construction & finish

Plastic lid and base; RAL7035 textured

IP Rating

IP30.

Weight

1.75kg (without batteries)

Operating conditions/temperature

-5ºC to +40ºC. Max relative humidity: 95%.

  • Model: CFP702-4
  • Shipping Weight: 2 kgs
  • Manufactured by: C-Tec
Ask a Question

£101.39 Ex VAT

Add to Cart:

Manufacturer Info

datasheet

Customers who bought this product also purchased...