Approvals/certifications |
Certifed to EN54 Parts 2 & 4 by the LPCB., Certified to EN54-13 by Kiwa Telefication.
|
Mains supply |
230V 50/60Hz.
|
Mains rated current |
350mA maximum.
|
Internal power supply |
19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
|
Total output current limited to |
1.5A @ 230Vac (ImaxA eq 146mA).
|
Quiescent current |
25mA (mains failed, internal sounder active, PSU & gen fault LED lit)
|
Max battery size and type |
2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah.
|
No. of detector zone circuits |
8 (Max. length per circuit is 500m).
|
Call point resistor value |
470 to 680Ω.
|
Max. devices per detector zone |
25 detectors (or 32 detectors/manual call points combined).
|
No. of conventional sounder circuits |
4 (Max. length per circuit is 500m).
|
EOL resistor value |
6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
|
Alarm voltage |
27V max, 20V min (final battery voltage)
|
Max. sounder output current |
4 x 200mA (800mA total).
|
Auxiliary relays |
Two: (1) Aux. Fire; (2) Fault. Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
|
Open collector outputs |
Two: (1) Reset (Active during reset cycle); (2) Remote (Active during any unsilenced fire condition provided all relevant delays have expired). Max. sink current 30mA, Max. open circuit voltag
|
Other outputs |
24V Aux. Power (Protected by a resettable fuse. 100mA min. hold current. Resets when fault removed).
|
Auxiliary inputs |
Two: (1) ‘Class Change’ (constant sounders); (2) Alert (pulsed sounders). Connect to 0V to trigger, Max. input voltage 27V (non-latching)
|
Engineer (AL3) functions |
Program coincidence (double knock); Invoke One Man Walk Test; Program delays; Set up zones for non-latching operation; Program sounders to resound (or not resound) when a new zone enters al
|
Expansion connections |
Yes – for optional network driver cards (one required per repeater system), relay output cards and EN54-13 sounder circuit interface boards.
|
Product dimensions (mm) |
380 W x 235 H x D 96mm (hole required for flush mounting = 367 W x 220 H x 75 D mm. No bezel required).
|
Construction & finish |
Plastic lid and base; RAL7035 textured
|
IP Rating |
IP30.
|
Weight |
1.75kg (without batteries)
|
Operating conditions/temperature |
-5ºC to +40ºC. Max relative humidity: 95%.
|