Fike Twinflex Manual Call Point

The Twinflex Manual Call Point (MCP) is a ‘resettable’ style MCP that has the option of being flush fitted if required. Once operated the device latches into the alarm position and requires manually resetting via a special key. The device has been designed to fit a standard UK single gang deep (47mm min) back box and each MCP comes supplied with a flush fitting adaptor. The device is fitted with a single colour red LED to indicate activation and End Of Line status.

This MCP is compatible with Fike’s Twinflex range of control panels and may be installed on the same zone as the Multipoint detector/sounder and associated Twinflex devices. Its operating parameters are configured using a DIL switch on the rear of the device.

Dimensions

Width x Height: 88mm x 88mm

Depth: Standard inc base 52mm

Depth: Flush mounted 25mm

Operating Temperature -10°C to +50°C
Voltage Range 20 to 35V DC
LED Indication

Activated: 0.5 Second Interval

End Of Line: 5 Second Interval

System Compatibility

Twinflex: V1 onwards

TwinflexPro: V1 onwards

Zone Current @ 24VDC

Quiescent: 50uA

Active: 16mA

SLU Rating 3
DLU Rating 16

 

  • Model: 402 0006
  • Shipping Weight: 0.5 kgs
  • Manufactured by: Fike
Ask a Question

£18.73 Ex VAT

Add to Cart:

Manufacturer Info

datasheet