FIKE (802 0006) Twinflex Input Output (I/O) Module
Twinflex Input / Output Module, Relay interfacing module with monitored input to provide shutdown and monitoring facilities from the Twinflex zone. Mounted in a standard double gang box, including two sets of 2A rated SPCO relay contacts, one monitored input aznd inbuilt ‘End of Line’.
The TWINFLEX I/O Module is available for interfacing to other systems in the field. This module is ideal for operating plant shutdown, door release mechanisms and access control override due to its wide range of switching configurations.
- The I/O Module connects to the zone wiring and provides a 230v AC rated DPCO relay contact, a low voltage SPCO contact for switching purposes and a single input for monitoring purposes.
- The unit may be programmed as required for a wide variety of input and output applications via the on board DIL switches.
- The input provided is fully fault monitored using a 3k3 end of line resistor; and activation is signalled with a 680R firing resistor, making this ideal for interfacing beam detectors and other ancillary devices.
- The module is available mounted in an industry standard double gang housing for ease of installation in either flush or surface mounting
Specifications:
- Dimensions: 146mm x 87mm x 41mm, 146mm x 87mm x 32mm
- Operating Temperature: -10°C to +50°C
- Voltage Range: 20 to 35v DC
- LED Indication: LED on
- Contact Rating: Relay 1: Max load 230V AC 3A (DPCO)
- Relay 3: Max load 30V DC 0.5A (SPCO)
- Fuses: 3.15A Antisurge 20mm Ceramic (eg. Bussman S505-3.15A)
- System Compatibility: Twinflex: V2 onwards
- TwinflexPro: V1 onwards
- Zone Current @ 24vdc: Quiescent: 0.29mA
- Active: 22.72mA
- SLU / DLU Rating: 4 SLU / 23 DL