EXP-PSU, External PSU with Wired Zones and Plug by Communicator Connection
Overview:
The EXP-PSU is a remote power supply intended for use in wired/wirefree alarm systems controlled by the i-onEX range of control units. This product offers the following benefits:
-
Powerful 3A supply. Independently charge and monitor one or two batteries. Mix and match batteries to meet system standby requirements: Maximum 2 x 17Ah.
-
Added flexibility for i-onEX installations. 10 zones onboard. 16 plug-by outputs for local connection of a communications device. Four transistorised outputs.
-
Easy to install and configure. Mains plus simple bus in/out connection. Semi-Auto addressing for speed and device numbering integrity. “Self installs” once addressed, go straight to adding detection zones.
-
Simple to service and support. Unique audible bus device locator. Power monitoring through keypads or web interface.
The power supply comprises a steel case containing a pcb (printed circuit board) and space for up to two 17Ah backup batteries. The unit can monitor and charge each battery independently and an installer can use combinations of batteries to meet their standby requirements.
The pcb also provides connectors for four transistorised outputs, 16 plug-by communicator outputs (mirroring those on the control unit), and up to 10 FSL (Fully Supervised Loop) or five CC (Closed Circuit) zones.
The EXP-PSU connects to the i-on control unit and the rest of the alarm system by means of the system bus, providing monitoring messages to the control unit over the bus. These messages include Remote PSU Fault, Remote AC Fail, Remote Battery Fail, and Remote Low Output Voltage.
During installation the EXP-PSU uses the same semi-automatic addressing procedure as other i-on expanders. The unit also provides an audible locator and allows power monitoring through the system keypads or the web-browser within the i-on control unit.
The EXP-PSU is designed and approved to be used as part of a Security Grade 2 or 3 system.
Specifications:
General
Product name
|
EXP-PSU.
|
Product Description
|
External PSU with wired zones and plug by communicator connection.
|
Manufacturer
|
Cooper Security Ltd.
|
Environmental
|
Class II.
|
Operating temperature
|
Tested -10 to +55°C.
|
Humidity
|
0 to 93% RH, non-condensing.
|
Case material
|
Steel.
|
Dimensions:
Size:
|
427 x 400 x 101, mm HxWxD.
|
Weight:
|
6 kg (without stand-by batteries).
|
Capacities
Zones
|
10 max
|
Outputs
|
16 plug-by communicator outputs, plus 4 open collector transistor outputs
|
Loudspeakers
|
1 output, minimum impedance 16 Ohms
|
Power Supply
This product complies with the requirements of EN50131-6 Type A power supply at Grade 3 and environmental class 2.
Power supply type
|
A
|
Mains power supply requirements
|
230VAC +10%/-15%, 350mA max, 50Hz.
|
Total power supply capacity:
|
3.0A
(of which 1.5A is used for battery recharge and 1.5A is available for powering the system).
|
Aux 1 12V supply*:
|
1A max
|
Aux 2 12V supply*:
|
1A max
|
Comms power supply*:
|
400mA max
|
12V Expander Bus OUT*:
|
400mA max
|
LS connectors
|
280mA in alarm.
|
*Note: The ratings given here represent the maximum current that can be drawn before triggering over-current protection.
EN50131-6 ratings
-
The EXP-PSU provides space for two 17Ah batteries, giving a total of 34Ah charge.
-
Under EN50131-1 for Security Grade 3 installations the required battery standby time is 30 hours, provided the system is fitted with an ATS4 communicator capable of transmitting a mains fail signal
-
This means that all the devices powered by those backup batteries, within the EXP-PSU, including the EXP-PSU itself, should together draw no more in total than an average of 1.1A over a 30 hour standby time. Note that for Security Grade 3 the i-on160EX or EXP-PSU must use a plug-by communicator, which may have its own power supply.
-
Under PD6662, battery standby time requirements for Security Grade 3 drop to 12 hours, provided the system is fitted with an ATS4 communicator capable of transmitting a mains fail signal.
-
For Security Grade 2 the required battery standby time is 12 hours. However, the total average current available over 12 hours from the EXP-PSU batteries is limited by the power supply to 1.5A. (The current is limited to 1.5A because when mains is present the 3.0A power supply reserves 2x750mA to recharge batteries, leaving 1.5A available to supply the system.)
-
To meet Security Grade 2 the control unit can be fitted with a plug-on communicator, for example the i-sd02.
-
The table below shows the current consumption of the EXP-PSU itself and each device that can be fitted to it.
EXP-PSU power requirement:
|
50mA quiescent.
100mA max
|
Keypad power requirement:
|
30mA (backlight off)
45mA (backlight on)
65mA (backlight on)
60mA in alarm
|
Wired Expander requirement
|
20mA max quiescent.
300mA in alarm if sounder connected.
|
Radio Expander requirement
|
40mA max quiescent
320mA in alarm if sounder connected.
|
Battery charging requirement:
|
750mA per battery (recharge within 24 hrs)
|
Plug-by Communicator pins require:
|
5mA each when active.
|
10 FSL zones
|
5mA
|
5 CCL zones
|
7mA
|
12V Bus output voltage range :
|
10±0.5V to 13.8V
|
Aux 1 & 2 12V output voltage range:
|
10±0.5V to 13.8V
|
Max p-to-p ripple voltage:
|
0.5V
|
Standby Battery:
|
12V, 17Ah sealed lead acid, 2 off (not supplied).
|
"Low battery" fault at:
|
< 12V
|
Aux power output fault at:
|
< 9V
|
Deep discharge protection at:
|
10±0.5V
|
Electromagnetic Compatibility
Immunity
|
Conforms to EN50130-4.
|
Emissions
|
Conforms to EN61000-6-3.
|
Outputs
O/P 1 - 4
|
Open collector transistor, +12VDC when inactive, 0V when active. 500mA max.
|
Plug-by O/P 1-16
|
Open collector transistor +12VDC when inactive, 0V when active, 50mA max.
|
LS (loudspeaker)
|
Min impedance 16 Ohm per output, current consumption = 280mA in alarm.
|
Fuses
-
The EXP-PSU has a replaceable T500mA mains fuse.
-
The Aux 1 and Aux 2 outputs are protected by separate F-1A 20mm fuse.
Electrical Safety - Conforms to EN60950-1.
Compliance Statements
-
The EXP-PSU is a type B ACE (as defined in EN50131-3 clause 8.7).
-
The EXP-PSU is compliant with EN50130-5 environmental class II.
-
The EXP-PSU is suitable for use in systems designed to comply with PD 6662: 2004 at grade 3.
-
When installed correctly the EXP-PSU is capable of compliance with EN50131 at Grade 3.
-
If the installer selects a non-compliant configuration then they must remove or adjust compliance labelling